29 CFR 1910.119(f) tells an employer what a written operating procedure for a covered process has to contain, how available it has to be, and how it stays current. 40 CFR 68.69 is the parallel rule for an EPA Risk Management Program process in Program 3. This is a reading of those sections for people who write the pages. It is general information, not a compliance opinion for any facility, and it is not a substitute for the text.

Clear instructions, consistent with the PSI

Both rules open the same way. The employer, or under the RMP rule the owner or operator, shall develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process, consistent with the process safety information.

"Clear" means an operator can carry the instruction out without inventing the missing half. "Consistent with the process safety information" means the limits, the chemicals, the equipment, and the safety systems in the procedure are the ones in the PSI. If the PSI and the procedure disagree, resolve the conflict before you issue the page.

The seven operating phases

1910.119(f)(1)(i) requires steps for each operating phase:

40 CFR 68.69(a)(1) lists the same seven phases in the same order, with the same sentence on emergency shutdown.

A set that covers normal operations and normal shutdown, and treats the other five as "see the emergency plan" or "use judgment," has not addressed the list. Temporary operations are on the list. Startup after a turnaround is a different document from initial startup. Emergency shutdown is a set of conditions and a named responsibility, not a cross-reference. Write the phase you named. The seven phases are different sequences.

Limits, consequences, and the corrective step

1910.119(f)(1)(ii) and 68.69(a)(2) require operating limits, the consequences of deviation, and the steps required to correct or avoid deviation.

A limit with no consequence is a number. A consequence with no step is a warning. The rule asks for all three, on the step where the operator compares the reading to the limit. The shape looks like this: "Header pressure: the range stated in the process safety information. Below the low end, the downstream unit loses feed. Above the high end, the relief path lifts. If pressure is outside the range, take the corrective step named here, or stop and notify the supervisor." The numbers have to be your numbers, taken from your PSI. The example is a shape. Copy your own limits.

Name the table in the step if the limit lives in a table. A cross-reference that takes a search is not a clear instruction.

Safety and health on the step that can hurt someone

1910.119(f)(1)(iii) and 68.69(a)(3) require safety and health considerations:

This block is often pasted from a safety data sheet and never tied to a step. The hazard information has to be available, and it has to show up where the operator can be exposed: which protective equipment before breaking a line, what to do if the detector alarms, which containers count as inventory in this process.

Safety systems, including the 2024 RMP sentence

1910.119(f)(1)(iv) requires safety systems and their functions. 68.69(a)(4) requires the same, and adds a Program 3 sentence the OSHA text does not have. 68.69(a)(4) also requires documentation when monitoring equipment associated with prevention and detection of accidental releases from covered processes is removed due to safety concerns from imminent natural hazards. That clause was added by the March 11, 2024 RMP amendments (89 FR 17689) and is in the current text of 68.69. EPA has since proposed further revisions to the 2024 rule (91 FR 8970, Feb. 24, 2026). Check the current eCFR text when you write the page. The two sections are not word-for-word copies. If Program 3 also applies, do not skip that sentence because you wrote the page from the OSHA text alone.

On the page, name the system where the operator depends on it. "Confirm the scrubber is in service and the room beacon is dark before you open the door." That is a safety-system step. "The unit is equipped with various safety systems" is not.

Accessible, current, and certified

1910.119(f)(2) and 68.69(b) require the procedures to be readily accessible to employees who work in or maintain the process. That includes the night shift and the copy that is not locked in an office.

1910.119(f)(3) requires review as often as necessary so the procedures reflect current practice, including changes in chemicals, technology, equipment, and facilities, and an annual certification that the procedures are current and accurate. 68.69(c) is the owner-or-operator version of that duty. Neither section prescribes a form. Both require the certification to mean current, and accurate.

1910.119(f)(4) and 68.69(d) require safe work practices for hazards during operations such as lockout/tagout, confined space entry, opening process equipment or piping, and control of entry by support personnel. Those practices apply to employees and to contractor employees. They sit next to operating procedures. They do not replace the operating phases.

If a change covered by management of change affects the procedures, 1910.119(l)(5) says the procedures shall be updated accordingly. The annual certification is not the first time a changed valve is allowed to appear in the text.

I write operating procedures for water, wastewater, and chemical plants. Your experts approve the procedure. Your facility does its own annual certification. This article is general information, not legal advice.